| Adaptable Modular Storage 2500 Controller Tray | Adaptable Modular Storage 2300/2100 Controller Tray | Standard Disk Expansion Tray | High Density Disk Expansion Tray | Adaptable Modular Storage 2500 Expansion Battery | ||
|---|---|---|---|---|---|---|
| Power supplies per tray | 2 | 2 | 2 | 4 | 1 | |
| Power supply type | AC | AC | AC | AC | AC | |
| Input voltage | 100V / 200V | 100V / 200V | 100V / 200V | 100V / 200V | 100V / 200V | |
| Operating voltage range | 89 to 127V / 178 to 254V | 89 to 127V / 178 to 254V | 89 to 127V / 178 to 254V | 89 to 127V / 178 to 254V | 89 to 127V / 178 to 254V | |
| Number of phases, cabling | Single phase plus ground (3 wire) | Single phase plus ground (3 wire) | Single phase plus ground (3 wire) | Single phase plus ground (3 wire) | Single phase plus ground (3 wire) | |
| Steady state current per power supply (amps) | 2.2x2 / 1.1x2 | 3.8x2 / 1.9x2 | 2.4x2 / 1.2x2 | 3.7x4 / 1.9x4 | 1.0 / 0.5 | |
| Breaking current (amps) | 16 | 16 | 16 | 16 | 16 | |
| Heat value (kJ/h) | 1,440 or less | 2,670 or less | 1,660 or less | 5,190 or less | 360 | |
| Required power | Steady state current (VA/W) | 440/400 or less | 760/740 or less | 480/460 or less | 1,480/1,440 or less | 100/100 |
| Starting state (VA/W) | 440/400 or less | 760/740 or less | 480/460 or less | 1,480/1,440 or less | 100/100 | |
| Electrical insulation performance | Insulation withstands voltage | AC 1,500V (10mA,1 min) | AC 1,500V (10mA,1 min) | AC 1,500V (10mA,1 min) | AC 1,500V (10mA,1 min) | AC 1,500V (10mA,1 min) |
| Insulation resistance | DC 500V, 10MΩ or more | DC 500V, 10MΩ or more | DC 500V, 10MΩ or more | DC 500V, 10MΩ or more | DC 500V, 10MΩ or more | |
| Time to fully charge battery | N/A | N/A | N/A | N/A | 24 hrs or less, depending on the amount of discharge | |
| Adaptable Modular Storage 2500DC Controller Tray | Adaptable Modular Storage 2500DC Disk Expansion Tray | Adaptable Modular Storage 2500DC Expansion Battery | ||
|---|---|---|---|---|
| Power supplies per tray | 2 | 2 | 1 | |
| Power supply type | DC | DC | DC | |
| Input voltage | -48 to -60 | -48 to -60 | -48 to -60 | |
| Operating voltage range (VDC) | -40 to 72 | -40 to 72 | -40 to 72 | |
| Steady state current per power supply (amps) | 4.2x2 | 4.6x2 | 1.5 | |
| Breaking current (amps) | 20 | 30 | N/A | |
| Heat value (kJ/h) | 1,460 or less | 1,605 or less | 260 or less | |
| Required power | Steady state current (VA/W) | 400/400 or less | 440/440 or less | 72/72 or less |
| Starting state (VA/W) | 400/400 or less | 440/440 or less | 72/72 or less | |
| Electrical insulation performance | Insulation withstands voltage | DC 1,000V (10mA,1 min) | DC 1,000V (10mA,1 min) | DC 1,000V (10mA,1 min) |
| Insulation resistance | DC 500V, 10MΩ or more | DC 500V, 10MΩ or more | DC 500V, 10MΩ or more | |
Products